Many HFC refrigerants have a high global warming potential (GWP), and therefore have the potential to contribute to climate change. Increasing concern due to the presence of greenhouse gases, including high GWP refrigerants, in the atmosphere and their effect on global climate is leading to international policies aimed at phasing down the use of refrigerants with high global warming potentials. The HVACF to 125F (18C to 52C). At the AHRI Standard 550/590 rating conditions, measured capacity when running the unit with R-516A was about 2% lower and EER was reduced by 3.5% to 4.0% compared to R-134a. Given these results, R-516A can be considered a design compatible alternative to R-134a in water chiller products.

Citation: 2018 Winter Conference, Chicago, IL, Conference Papers

Product Details

Published: 2018 Number of Pages: 8Units of Measure:DualFile Size: 1 file , 660 KB Product Code(s): D-CH-18-C063